Operation Phase Monitoring Relays will protect against premature equipment failure caused by voltage faults on three-phase systems. These devices protect against unbalanced voltages or single phasing regardless of any regenerative voltages. The relay is energized when the phase sequence and all voltages are correct. Any one of four fault conditions will de-energize the relay. Re-energization is automatic upon correction of the fault. An LED indicates normal and tripped conditions. |
| AC OPERATED | | NTE Type No. | Nom. Volt. | Contact Arr. | Adjustable Under Voltage Drop-Out | Input Current Nom. | Max. Contact Cur, @ 30VDC or 240VAC | | R68-5A10-240 | 208/240VAC | SPDT | 180-230V | 14/12mA | 10A | | R68-5A10-480 | 480VAC | SPDT | 360-460V | 6mA | 10A |
| ACCESSORIES | | Mounting Styles | Description | NTE Type No. | | Surface Mount | 8-Pin Octal | R95-101 | | Panel Mount | 8-Pin Octal | R95-118 | | DIN Rail Mount | 8-Pin Octal | R95-113 |
| | Dimensional Drawing
SPDT, 1 Form "C" 
Electrical Specifications Contact Rating: 10 Amps resistive at 240VAC, 1/2 HP at 240VAC, 10 Amps resistive at 30VDC Life: 500,000 operations at full load Mechanical Life: 7,000,000 operations at no load Input Nominal Input Voltage: See Chart Steady State Input Current: See Chart Operational Characteristics Timing Values: Operate Time: 50mS Release Time: 50mS fixed on phase loss, phase unbalance, and phase reversal; 0.1-20sec adjustable on undervoltage only Hysteresis: 2-3% Protection Transient: 10,000V for 20µs Indicator LED: Red LED steady when all conditions are normal, and flashing when a fault condition has occurred Reset: Automatic upon correction of fault Environmental Characteristics Operating: -28°C to +65°C |