Features
  • 8 programmable timing modes (4 on 8-Pin types)
  • 0.1 sec. to 100 min. programmable timing range
  • Universal (24 - 240VAC/VDC)
  • 10A output relay with DPDT contacts
  • DIP switch selection of timing mode and range
  • Knob and dial scale for setting actual delay time
  • R64 SeriesUL CSA logo

    Programmable, DPDT, 10 Amp, AC or DC,
    Multifunctional Time Delay Relay
    Photo of R64 Series Relay

    AC or DC OPERATED
    NTE
    Type No.
    No.
    of
    Pins
    Timing
    Adj
    Range
    Contact
    Arr.
    Nom
    Vltg
    AC/DC
    Nom
    Power
    Max.
    Contact
    Cur. @
    30VDC
    277VAC
    R64-11AD10-480.1sec.
    to
    100min.
    DPDT24
    to
    240
    1W@24V
    5W@120V
    10W@240V
    10A
    R64-11AD10-8110.1sec.
    to
    100min.
    DPDT24
    to
    240
    1W@24V
    5W@120V
    10W@240V
    10A
    Note: R64-11AD10-X where "X" indicates the number of
    timing functions.

    ACCESSORIES
    Mounting StylesDescriptionNTE Type No.
    Surface Mount8-Pin OctalR95-101
    11-Pin OctalR95-104
    Panel Mount8-Pin OctalR95-118
    11-Pin OctalR95-119
    DIN Rail Mount8-Pin OctalR95-113
    R95-181
    11-Pin OctalR95-114
    R95-182

    DIP Switch Layout

      

    Electrical Specifications

    Contact
    Rating: 10 Amps @ 30VDC or 277VAC, resistive;
    1/2 HP @ 250VAC; 1/3 HP @ 120VAC
    Life: 100,000 operations at minimum rated load
    Mechanical Life: 10,000,000 operations

    Input
    Nominal Input Voltage: 24 - 240V ±15%, 50/60Hz AC or DC
    Nominal Power: See Chart

    Timing
    Timing Ranges: 0.1 to 1.0 / 1.0 to 10 / 10 to 100 sec.;
    Timing Ranges: 0.1 to 1.0 / 1.0 to 10 / 10 to 100 min.
    Timing Adjustments: Knob adjustable within selected range
    Tolerance: -0, +20% of max. specified at high end timing range; min. specified, or less at low end
    Delta Time (for AC units add ±1 cycle 60Hz): ±10%
    Repeatability (for AC units add ±1 cycle 60Hz): ±2% - including first cycle of operation
    Reset Time (power interruption): 45mS Typ.; 60mS Max.
    Minimum Pulse Width, Control: 50mS
    Recycle Time: 45mS Typ.; 60mS Max.

    Protection
    Transient: Yes
    Dielectric Strength:
          Between Open Contacts:
    1000Vrms, 60Hz
          Between All Other Conductors: 1500Vrms, 60Hz

    Environmental Characteristics
    Operating: -10°C to +55°C
    Storage: -20°C to +70°C
    Humidity: 85% relative humidity, non-condensing

    Weight
    Std: 4.3ozs. (122g) approx.

    Timing Function Descriptions
    Delay On Operate
    8-Pin Type: Output relay is energized at the completion of the time interval which is initiated by the application of input voltage.
    11-Pin Type: Same as above except, closing the control switch after time out will de-energize the relay and reset the timer. Opening the switch will initiate another time interval. Closing the control switch during timing will reset the time to zero and inhibit timing until opened again.

    Interval On (Input Controlled)
    8-Pin Type: Output relay is energized by the application of input voltage. The time interval is initiated at the same time with the relay de-energized at the completion of the time interval.
    11-Pin Type: Same as above. Closing the control switch will have no effect on timing or the state of the relay.

    Recycler (Initially Off)
    8-Pin Type: Output relay will begin cycling at a 50% duty cycle with the application of input power. The initial state of the relay will be de-energized.
    11-Pin Type: Same as above except, closing the control switch will de-energize the relay and inhibit timing until it is once again opened, at which time it will start from zero time.

    Recycler (Initially On)
    8-Pin Type: Output relay will begin cycling at a 50% duty cycle with the application of input power. The initial state of the relay will be energized.
    11-Pin Type: Same as above except, closing the control switch will energize the relay and inhibit timing until it is once again opened, at which time it will start from zero time.

    Delay On Release
    11-Pin Only: Output relay is energized by the closing of the control switch with the input applied of the application of input voltage with the control switch already closed.

    The time interval will be initiated by the opening of the control switch with the relay de-energized at the completion of the time interval. Closing the control switch after time out will energize the relay in preparation for another time interval. Closing the switch during timing will reset the time to zero and inhibit timing until opened again.

    Inverted Delay On Release
    8-Pin Type: No Time Delay - Instantly ON
    11-Pin Type: Output relay will energize with the application of the input voltage when the control switch is open. Control switch closing will de-energize the relay. A timing interval will be initiated with the opening of the control switch, at the completion of which the relay will energize. With the control switch closed upon application of input voltage, the relay will wait until the control switch is opened to initiate a time interval after which the relay will energize. Closing the control switch during timing will reset the time to zero and inhibit timing until opened again.

    Interval On (Switch Controlled)
    11-Pin Only: Output relay is energized by the application of input voltage with the control switch closed or the closing of the control switch with the input applied. Immediately upon either, timing is initiated with the relay de-energized at the completion of the time interval. Closing the control switch after time out will reset the timer, energize the relay, and initiate another time interval. Closing the control switch during timing will have no effect on timing or the state of the relay.

    Interval Off
    11-Pin Only:Output relay will initially be energized with the application of the input voltage when the control switch is open. Control switch closing will de-energize the relay and start a time interval. At the completion of the time interval, the relay will energize. With the control switch closed upon application of input voltage, a time interval will be initiated after which the relay will energize. Closing of the control switch during timing will have no effect on timing or the state of the relay.

     Home Back

    Safe & Secure online shopping guaranteed.

    90 Day Warranty

    Price Match Guarantee

    Call our Customer Service at 818-675-9000 if you find a lower price on any of our items and we'll match it.*

    Coupons & Promotions Refer A Friend Free Shipping

    © 1995-2014, All material on this site is copyrighted by HobbyTron.com or the product itself.

    Exclusions


    Facebook Google+ Instagram Twitter YouTube Pinterest Vine Tumblr

    X