 | NTE Type No. | Current Rating (Amps) | Typical Resistance (Ohms) | | R58-1A | 1.0 | 1.35 | | R58-2A | 2.0 | 0.32 | | R58-3A | 3.0 | 0.18 | | R58-4A | 4.0 | 0.10 | | R58-5A | 5.0 | 0.026 | | R58-6A | 6.0 | 0.026 | | R58-7A | 7.0 | 0.020 | | R58-8A | 8.0 | 0.020 | | R58-10A | 10.0 | 0.014 | | R58-12A | 12.0 | 0.010 | | R58-15A | 15.0 | 0.010 | | R58-20A | 20.0 | 0.006 | | R58-25A | 25.0 | 0.005 | | R58-30A | 30.0 | 0.004 | | R58-35A | 35.0 | 0.004 |
Trip Times
| 1 to 4 Amp Types | 5 to 35 Amp Types | Rated Load | Trip Times | Rated Load | Trip Times | | 100% | No Trip | 100% | No Trip | | 145% | Trip in 1 Hr. | 145% | Trip in 1 Hr. | | 200% | 10 to 45 Sec. | 200% | 6.0 to 30 Sec. | | 400% | 3.0 to 14 Sec. | 400% | 1.6 to 4.5 Sec. | | 600% | 1.4 to 7.0 Sec. | 600% | 0.6 to 1.7 Sec. | | 800% | 0.75 to 4.3 Sec. | 800% | 0.25 to 0.9 Sec. | | 1000% | 0.5 to 3.4 Sec. | 1000% | 0.15 to 0.65 Sec. |
| 

Electrical Specifications
Electrical Characteristics (@ 25°C) Calibration: Will continuously carry 100% of rating. May trip between 101% and 144%, but must trip at 145% of rating at +25°C. Maximum Operating Voltages:50 VDC; 250 VAC, @ 50/60 Hz Dielectric Strength: 1500VAC RMS Resettable Overload Capacity:Ten times rated current Interrupt Capacity: 2000 Amps @ 50VDC 1000 Amps @ 250VAC Mechanical Characteristics Termination .250" (6.35mm) Quick Connect Terminals NOTE: Soldering to terminals is not recommended. Shock: Withstands to 10g Endurance Cycling: Over 1000 cycles @ 200% of rated load Vibration: Withstands to 10g @ 10 to 55 Hz. Weight: Less than 1.5ozs. (42.5g) NOTE: 30A and 35A devices NOT UL or CSA. |